
ATI A15/66 Residual Sulfite Monitor
28
O&M Manual
Rev-W (8/10)
PULSE WIDTH MODULATION (PWM) CONTROL
Relays A and B can also be used for control of chemical feed systems using a pulse width control
mode. In pulse width control, the relay will close for a variable time period that is linearly proportional to
the deviation of the measured value from your setpoint. This type of output is not as common as PFM,
but can be used when controlling a solenoid feed valve or for running a pump for variable time periods.
To use PWM control, the relay must be configured for PWM control in steps 14 or 16 of the configuration
menu. For chemical feed control, you will normally want to set the alarm relays to low in steps 15 and 17.
To set up a control system using PWM control, you must program a setpoint, a proportional band,
and a frequency range. The setpoint is the maximum value that you would want to maintain. When the
measured value reaches the setpoint, the output duration will be at a minimum. To set the setpoint, press
the MODE key until the display reads “SA X.XX PPM W L”. Then press the CAL key once. The
display will read “CAL SA S: X.XX”. Use the UP and DOWN keys to select the desired setpoint. Then
press ENTER.
The next setting is the proportional band setting. After pressing ENTER in the previous section,
the display will indicate “CAL SA BP: X.XX”. The proportional band is the amount of deviation from the
setpoint required for the duration of the relay closure to reach a maximum. Use the UP and DOWN keys
to select the proportional band and then press ENTER.
The final setting is the maximum pulse duration (time) required to control the feed device. This
duration will be dependent on the type of equipment you are trying to control. The monitor can be
adjusted for pulse durations of 0-99.0 seconds. When you press ENTER in the previous step, the display
will change to “CAL SA T: 20.0 s” This is the default setting of 0-20 seconds. Left at this value, the relay
will close for 20 seconds when the measured value at maximum deviation from the setpoint and will not
close at all when the measured value reaches the setpoint. Enter the value you want for the maximum
pulses per minute and press ENTER. The display will flash UPDATE and the relay will begin to operate
in accordance with the programming entered.
As an example, assume that you want to use relay B to control a solenoid valve feeding sodium
bisulfite into a tank. You would like to maintain a sulfite value between 0.5 and 1.0 PPM and your
variation in feed time is estimated at 0-15 seconds. Programming would then be as follows.
7. In the configuration menu, step 16, select PWM.
8. In the configuration menu, step 17, select LO
9. Go to the B relay display (display D5, page 20) and press CAL.
10. Adjust the setpoint value to 1.00 and press ENTER.
11. Adjust the proportional band value to 0.50 and press ENTER
12. Adjust the time to 15.0 and press ENTER.
With the programming just entered, relay B will close for 15 seconds when the measured sulfite
value is below 0.50 PPM. When the value reaches 0.75 PPM, the relay will close for 7.5 seconds (out of
a 15 second cycle time). When the value reaches 1.00 PPM, the relay will stop remain open.
You can verify the operation of the relay by placing the monitor into simulate (SIM) mode of
operation. By manually increasing or decreasing the displayed value, you will hear the change in the
relay pulses. Note that the “” symbol indicating the relay condition will change from open to closed
indicating the state of the relay.
Comentarios a estos manuales